- 영문명
- Validation of FDS for Pool Fire in Three Rooms Connected to Ventilation Network
- 발행기관
- 한국화재소방학회
- 저자명
- 배용범(Bae, Young-Bum) 이상규(Lee, Sang-Kyu) 신병수(Shin, Byung-Soo) 김남석(Kim, Nam-Seok) 금오현(Keum, O-Hyun) 박종석(Park, Jong-Seok)
- 간행물 정보
- 『한국화재소방학회 학술대회논문집』2011년도 춘계학술논문발표회 논문집, 9~15쪽, 전체 7쪽
- 주제분류
- 공학 > 공학일반
- 파일형태
- 발행일자
- 2011.04.30
국문 초록
영문 초록
This study aims to validate predictive capabilities of FDS for the pool fire in three rooms connected to ventilation network. The three rooms in real scale fire test facility are configured to be similar to that of nuclear power plant in size, ventilation condition, construction material, etc. Basically three rooms are confined to the other area except two open doors and two ventilation duct in each room. The real scale fire test was conducted with these conditions and the predictive capabilities of FDS will be validated by comparing FDS simulation results with experimental data from the temperature, heat flux, and concentration point of view. This study concludes that temperature from FDS is about 25 % lower deviation from the experiment, and heat flux from FDS is about 5% deviation.