- 영문명
- Indoor and Outdoor Distribution of Legionella spp and Microbes on Cooling Towers Water of Central Air Conditioning Facilites
- 발행기관
- 한국환경보건학회
- 저자명
- 방선재 이철민 김윤신 선우영
- 간행물 정보
- 『한국환경보건학회지』제28권 제3호, 39~48쪽, 전체 10쪽
- 주제분류
- 공학 > 환경공학
- 파일형태
- 발행일자
- 2002.09.30
국문 초록
영문 초록
Cooling towers water has frequently been known as a source of infection in outbreaks of Legionnaires disease and a source of indoor air pollution. However, there have been a few reports on the presence of Legionella in cooling towers water and aerosols of various public facilities. This study was carried out to investigate the indoor and outdoor dis-tribution of Legionella spp and microbe from 132 cooling towers water of public facilities detected 1. pneumophila in Seoul and Gyeonggi-Do areas. The results showed that the Lpneumophila among the selected 132 cooling towers was detected mostly in July (12.0%), followed by August (4.0%) and June, September no-detected. The 1. pneumophiia in public facilities was detected mostly in department store (27.3%), followed by hospital (8.7%), office building (5.9%), big market (5.0%) and hotel, subway no-detected. The pH values of cooling towers water with presence of 1. pneumophila showed mostly 8.0 or higher (9.5%), followed by 7.0~8.0 (6.8%), lower 7.0 no-detected. The tem-perature of cooling towers water with presence of L pnemophila showed mostly 30℃ or higher (9.8%), followed by 26~30℃ (6.9%), lower 25℃ no-detected. The turbidity of cooling towers water with presence of 1. pneumaphila showed mostly 1-2 M (8.8%), followed by above 2 NTU (5.9%), lower 1 NTU no-detected. The correlation coef-ficient between indoor and outdoor concentration of microbes in public facilities showed 0.67 in Legionella spy. (p>0.05), 0.93 in bacteria (p<0.01), 0.94 in fungus (p<0.01), 0.98 in coilform (p<0.01), respectively.
목차
ABSTRACT
Ⅰ.서론
Ⅱ.연구방법
Ⅲ.결과 및 고찰
Ⅳ.결론
참고문헌
해당간행물 수록 논문
참고문헌
최근 이용한 논문
교보eBook 첫 방문을 환영 합니다!
신규가입 혜택 지급이 완료 되었습니다.
바로 사용 가능한 교보e캐시 1,000원 (유효기간 7일)
지금 바로 교보eBook의 다양한 콘텐츠를 이용해 보세요!